Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98
55
Shown below are three examples of programmable I/O statements that can be used on the 4734
to obtain customized status outputs.
EXAMPLE 1: The following statment will cause Terminal 15 on the 4720 to produce an
active low output whenever there is a fire alarm in any area.
TER15 = FIRE
EXAMPLE 2: The following statement will cause Terminal 16 on the 4720 to produce an
active low output whenever there is an intrusion alarm in any area.
TER16 = INTRU
EXAMPLE 3: The following statement will cause the X-10 Module Address #1 from the
first house code to be activated whenever Area #1 (or a non-area system) is in entry or exit
delay. The module could then be used to activate entry lighting. The unit will be deacti-
vated when the entry/exit delay end or the area is disarmed.
X10[1].0 = (AEXIT[1] or AENTRY[1])