Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98
37
NO SHUTD#1:NO
If this option is selected, the bell will not shut down until the panel is disarmed. The display
now advances to the next touchpad panic zone.
5.17 Area Options (Menu 16)
SPLIT ARM:NO
This option must be selected in order for the area control features to operate.
AUTO CLOSE:NO
Selecting this option causes the system to arm itself automatically if the panel is not armed at
the end of any time window in the Auto Close Window Group (CL WIN GRP).
NOTE UL installations must NOT select this option.
AUTO OPEN:NO
Selecting this option causes the system to disarm itself automatically if the panel is not dis-
armed at the end of any time window in the Auto Open Window Group (OP WIN GRP).
EXAMPLE: Suppose you select Window Group #1, to which you’ve assigned the time
windows shown below, for OP WIN GRP.
Time Window #3
— Monday-Friday, 7:59-8:00 AM
Time Window #4
— Monday-Friday, 1:59-2:00 PM
Time Window #5
— Saturday, 9:59-10:00 AM
Time Window #6
— Saturday, 10:59-11:00 AM
On Monday through Friday, if no one has disarmed the system by 8:00 AM, the system
will disarm automatically at 8:00 AM (end of Window #3). If someone arms the system
later in the morning (before leaving the office for lunch, for example) and no one disarms
it by 2:00 PM, the system will disarm automatically at 2:00 PM (end of Window #4).
On Saturday, if no one has disarmed the system by 10:00 AM (end of Window #5), the
system will disarm automatically. If the system has not been disarmed manually by 11:00
AM (end of Window #6), it will disarm automatically at that time.
NOTE When programming auto open/close time windows, the start time must be one (1) minute
before the end time.