Clearance:
Dimension
Measured From:
USA Only Canada Only
A: Mantel
Height
18” (457mm) 18” (457mm) Minimum (See Page 86)
B: Sidewall 18” (457mm) 24” (610mm)
Side of fi replace
opening
C: Ceiling 46” (1168mm) 46” (1168mm)
Top of fi replace
opening
D: Mantel
Depth
10” (254mm) 10” (254mm) Maximum
(See Page 86)
E: Alcove
Width
N/A N/A
Approved for Single
Sidewall only
F: Alcove
Depth
N/A N/A
Approved for Single
Sidewall only
G: Thermal
Protection
Height
1/2” (13mm) 1/2” (13mm)
Bottom to top of
Protection.
H: Hearth
Width
40” (1016mm) 40” (1016mm) Edge to Edge of Hearth
I: Hearth
Depth
18 ” (457mm) 18 ” (457mm) Front of Hearth to Wall
J: Facing
Height**
52-1/2”
(1334mm)
51-1/2”
(1308mm)
Floor to Facing
Height**
K: Facing
Width**
44” (1118mm) 60” (1524mm)
Edge to Edge of
Facing**
**Required non-combustible facing.
172 June 2007 Regency Product Specifi cations Book
Wood Fireplaces
Wood Fireplaces
NOTES:
1) Minimum Chase sizes must be met according to the framing
directions (page 149). US Installations will require a minimum
ventilation with one 30 sq. in. (194 sq. cm.) opening grill (air is
drawn from within the home not outside).
2) Mantel min. Height of 18” (457mm) from top of louver opening to
underneath mantel or 55 1/2” (1410mm) from bottom of unit.
3) Minimum non-combustible facing must be installed according to
the table on this page. Finishing material to be installed on top of
this.
4) Framing is slightly larger than unit dimensions to allow for easier
installation (50 3/4”, 1289mm h x 44”, 1118mm w)
5) Must maintain a min. of 46” (1168mm) from top of louver opening
to fi nished ceiling.
6) Sidewall clearances, as detailed on this page, must be maintained
according to your location.
7) Hearth must be a min. 40” (1016mm) wide x 18” (457mm) deep
and 1/2” (127mm) thick.
Clearances Requirements
No combustible materials on the face of unit.
Required Hearth must be non-combustible and will require
thermal protection. Minimum thermal protection must have
a "k" factor of 20.07 (in Canada), 0.84 (in US).
R90 Wood FireplaceR90 Wood Fireplace
Combustibles may not extend to unit face.
Do not notch wallboard around standoffs.
The R90 may be placed on or near construction materials. The
combustion air kit, fi re stop spacer and roof fl ashings (not chase
ashings) may be placed directly on or against normal construction
materials. The chimney requires a minimum 2" (51mm) clearance. A
combustible mantle (to a depth of 10", 254mm) may be installed no
closer than 18" (457mm) above the warm air vent or 55-1/2" (1410mm)
from bottom of unit.
The chimney must be enclosed when installed in or passing through a
living area where combustible material or people may come in contact
with it. This is important to prevent possible personal injury or fi re
hazard.
For any further information, please call your dealer. Special restrictions
apply to the front and facing of the fi replace and nearby walls.
WARNING: If insulation is used, do not place the unit against it. Insulation
or vapor barriers, if used, must be secured to assure insulation and vapor
barriers remain in place and do not affect the required air spaces.
WARNING: Do not pack or fi ll required air spaces with insulation or other
material. No material of any kind is allowed in these areas.
NOTES:
1) Do not insulate the chase cavity with blown or fi ll type insulation
materials.
2) Local codes may not require a fi restop at the ceiling level for outside
chase installations; however, it is recommended for safety and the
reduction of heat loss.
3) We recommend that you insulate at least the fi rst oor of the chase
to prevent heat loss.
4) Some local codes require 1 hour fi re rating on one or all sides of
re chases. Check with your local authorities.